![]() |
JMC Limited electrical testing services |
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
............Home | .....Services | .....About Us | .... Contuct Us |
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]() |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
services --->Fixed electrical wiring systems |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
Fixed electrical wiring systems
Electrical fixed wiring testing for all types of industry, providing you with reports that help you maintain a safe environment. We are NICEIC approved, which is recognised by all industries, allowing our reports to be presented on NICEIC forms. Re-assurance that you are safe
PERIODIC INSPECTION AND TESTING OF ELECTRICAL INSTALLATIONS
1.0 PURPOSE
To verify as far as is reasonably practicable within the limits of this specification that the electrical installation is in a safe condition and thereby complies with the fundamental requirements of BS 7671 IEE Wiring Regulations (current Edition) and the Electricity at Work Regulations (1989) Electricity at Work Regulations ( Northern Ireland ) 1991.
2.0 INSTALLATION DOCUMENTATION
2.1 Diagrams, charts or tables and previous periodic or routine inspection reports should be made available to the Inspecting Engineer, as required by BS 7671.
3.0 METHOD
3.1 To carry out a thorough visual inspection of the electrical installation where practicable with regard to the following:
3.2 To supplement the visual inspection with such electrical testing as considered necessary for protection against:
4.0 VISUAL INSPECTION
A 100% visual inspection of the fixed electrical installation, including an internal inspection of distribution boards, where practicable to include the following:
5.0 TESTING SCHEDULE
5.1 Continuity testing of protective conductors to include: -
5.2 Polarity Testing
5.3 Earth loop impedance
Earth loop impedance tests to be carried out at locations indicated below: -
5.4 Operating devices for isolation and switching
These are to be checked for effectiveness and to ensure adequate and correct labelling.
5.5 Operation of Residual Current Devices (RCD’s) 100% of RCD’s will be tested for tripping time at half rated, full rated and five times rated tripping current across positive and negative cycles, where practicable.
5.6 Prospective fault current Tests to be carried out at the origin and at each distribution board.
5.7 Insulation Resistance Testing Insulation Resistance tests will be carried out at the discretion of the inspecting engineer with due regards to age, condition and visual inspection, up to 10% of the circuits. From the results of the sample insulation resistance testing, if an unacceptable high failure rate is found further testing will be recommended.
6.0 REPORTING
Reports to be completed using the JMC reporting system.
The reported defects and remedial actions are prioritised as follows:
(This does not necessarily imply that the electrical installation inspected is unsafe.)
7.0 LIMITATIONS
7.1 The inspection and testing will be carried out where practicable at the discretion of the Inspecting Engineer, taking into account availability and accessibility.
7.2 Cables concealed within trunking and conduits, or cables and conduits concealed under floors, in inaccessible roof spaces and generally within the fabric of the building or underground, will not be visually inspected.
7.3 Insulation resistance tests will not be carried out on circuits and/or sections of the installation, which contain electronic or similar sensitive circuitry.
8.0 SPECIFICATION (A.)
8.1 This requires full testing and reporting of each and every circuit in the property. This can be time consuming therefore a bit more expensive.
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Home | Services | About Us | Contact Us Copyright 2008 All Rights Reserved, JMC Electrical Ltd |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||